IEC 61850

IEC 61850 edition 1 vs. edition 2

The first version of IEC 61850 was published between 2001 and 2004. Since then, each part has been revised and extended into an edition 2 to improve its content and respond to new needs of the power sector.

IEC 61850 Axon Group blog

The first version of IEC 61850 was published between 2001 and 2004. Since then, each part has been revised and extended into an edition 2 to improve its content and respond to new needs of the power sector.

Main changes by part of the standard

Part 1 extended the scope to power quality, statistics, generation, distribution, and Smart Grid. Part 3 added product safety and EMC requirements; part 5 extended the model to communication between substations.

Part 7-1 included statistical data, proxies, gateways, LD hierarchies, and time synchronization; 8-1, Gigabit Ethernet and link-layer redundancy; and part 10 updated the server tests and added tests for clients and GOOSE performance.

Key fact

The first edition generated around 800 TISSUEs with comments and solutions to the problems found.

2001 – 2004

Edition 1

First publication

  • Object names of up to 64 characters
  • Included GSSE
  • Change monitoring
  • Close to 800 improvement TISSUEs

Revision

Edition 2

More scope and redundancy

  • Names of up to 128 characters
  • Redundancy with PRP and HSR
  • Logical device hierarchy
  • Service tracking and security mechanisms

Compatibility between versions

It received special attention: the basic point is to know which edition each device supports, because servers of both editions coexist. At the communications level there are no major issues, and ambiguities in buffered reports were resolved.

A single SCADA client receives MMS reports from an edition 1 IED and an edition 2 IED connected to the same network: the two editions coexistSCADA clientIEC 61850 NETWORK · MMSEdition 1 IED2001 – 2004Edition 2 IEDrevisionnames of up to 64characters · GSSEnames of up to 128characters · PRP and HSRA single SCADA client receives MMS reports from an edition 1 IED and an edition 2 IED connected to the same network: the two editions coexistSCADA clientIEC 61850 NETWORK · MMSIEDedition 1IEDedition 2names up to 64characters · GSSEnames up to 128characters · PRP/HSR
Figure 1. Edition 1 and edition 2 servers coexist on the same network with a single client.
  • MMS reports

Conclusion

Edition 2 improves and extends edition 1, with new tests and functions for modeling the power system, and it is compatible with it: servers of different editions can coexist.

Article written by

Iván Darío Claros, PhD

R&D Manager · Axon Group

View more articles
Related product

Put it into practice with AG

See the technical glossary ›

AG Empowering

Want to train on this topic?

Explore the AG Empowering programs and bootcamps and keep learning with our team of specialists.

Go to AG Empowering

Questions about our training?

Get in touch and we will help you find the right program for your team.