T0 > T3Prevents disconnections due to inactivity
T1 > T2Prevents disconnections due to missing acknowledgment
K > WMaintains performance under heavy traffic

Parameters you can optimize

The link address is specific to IEC 60870-5-101 and physically addresses the devices (one or two octets). The cause of transmission can be one octet if the channel has a single master.

The ASDU address logically groups several links, and the IOA is the address of the process signals: one, two, or three octets depending on the number of signals.

  • Link address: one or two octets
  • Cause of transmission: one octet with a single master; two if there are several
  • ASDU: 1 to 254 (one octet) or 1 to 65,534 (two octets)
  • IOA: up to 255, 65,535, or 16,777,215 depending on its octets

Key fact

Under the IEC 60870-5-101/104 standards, the size of some parameters can be adjusted to optimize channel bandwidth.

Originator Address

On some devices, the size of the cause of transmission appears as Originator Address: enabled means two octets and disabled means one. It must match between slave and master; otherwise, the information is rejected as coming from an unauthorized source.

Fields of an IEC 60870-5-101/104 frame: link address (101 only), type, VSQ, cause of transmission with the optional Originator Address, ASDU address, IOA, and data; the cause, the ASDU, the IOA, and the link address can change sizeLink101 onlyType1 oct.VSQ1 oct.COT1 oct.OAoptionalASDU1–2 oct.IOA1–3 oct.DatavariableLINKASDULink address: physically addresses the device; it exists only in IEC 60870-5-101.COT + OA: with the Originator Address enabled they take 2 octets; it must matchon the master and the slave, or the information is rejected.ASDU: 1 to 254 with 1 octet, or 1 to 65,534 with 2.IOA: up to 255, 65,535, or 16,777,215 signals with 1, 2, or 3 octets.Fields of an IEC 60870-5-101/104 frame: link address (101 only), type, VSQ, cause of transmission with the optional Originator Address, ASDU address, IOA, and data; the cause, the ASDU, the IOA, and the link address can change sizeFRAME FIELDSLink address1–2 octets · 101 onlyType1 octetVSQ1 octetCause (COT)1 octetOriginator (OA)+1 octet, optionalASDU address1–2 octetsIOA1–3 octetsDatavariableThe Originator Address must match onthe master and the slave, or theinformation is rejected.
Figure 1. Fields of an IEC 60870-5-101/104 frame; in blue, the ones that change size.
  • Configurable size

Timers and windows in IEC 60870-5-104

T0 and T3 supervise communication when there is no data: T0 always greater than T3. T1 and T2 supervise it under traffic: T1 always greater than T2. K and W protect performance under heavy traffic: K always greater than W.

On high-latency channels, such as radio or satellite, T1 can be increased to allow more time for acknowledgment, and T2 reduced to acknowledge faster.

Article written by

Eng. Alonso Rojas Rojas

Telecontrol specialist · Axon Group

View more articles
Related products

Put it into practice with AG

See the technical glossary ›

AG Empowering

Want to train on this topic?

Explore the AG Empowering programs and bootcamps and keep learning with our team of specialists.

Go to AG Empowering

Questions about our training?

Get in touch and we will help you find the right program for your team.